0x3220

Remedy
  • Check mains voltage.
  • 0x2D87 (P105.00)Check DC-bus voltage.
  • Check mains settings.
  • Check fuses.
Cause

DC-bus voltage has fallen below the error threshold for undervoltage. The error threshold (display in 0x2540:003 (P208.03)) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

Description

Fault - DC bus undervoltage

Keypad display

DC Bus UV

Fault message ID
12832
Severity/response

Trouble