0x4210

Remedy
  • Check mains voltage.
  • Provide for a sufficient cooling of the device. In case of a 100 % load, 60 C to +70°C are normal. Display of the heatsink temperature in 0x2D84:001 (P117.01).
  • Clean fan and ventilation slots. If required, replace fan.
  • Reduce switching frequency 0x2939 (P305.00)
Cause

The heatsink temperature of the power unit (display in 0x2D84:001 (P117.01)) has exceeded the fixed error threshold (100 °C).

  • Ambient temperature too high.
  • Fan or ventilation slots are polluted.
  • Fan is defective.
Description

Fault - Power unit overtemperature

Keypad display

PU Overtemp.

Fault message ID
16912
Severity/response

Fault