Skip to main content

0x7180

Remedy
  • Check motor load.
  • Check drive dimensioning.
  • Check warning threshold or error threshold set in 0x2D46:001 (P353.01).
Cause

The motor current has exceeded the warning/ error threshold for the motor current monitoring set in 0x2D46:001 (P353.01).

Description

Motor overcurrent

Keypad display

Mot max current

Fault message ID
29056
Severity/response

Fault (configurable)

  • The event can only be reset after a blocking time. Setting parameters: 0x2D46:002 (P353.02)
Severity/response - 1

Blocking time: 1 s

Severity/response - 2

Setting parameters: 0x2D46:002 (P353.02)