0x7305

Remedy
  • Check the encoder connection.
  • Check encoder cable for wire breakage.
  • Check encoder current supply.
Cause

The encoder signal loss monitoring function has detected a failure of the encoder signal.

Description

Encoder open circuit

Keypad display

Encoder error

Fault message ID
29445
Severity/response

Warning (configurable) Setting parameters: 0x2C45 (P342.00)

Severity/response - 2

Setting parameters: 0x2C45 (P342.00)