Skip to main content

0x7691

Remedy

1. Execute device command "Load default settings" 0x2022:001 (P700.01). 2. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command.

Cause

The parameter settings saved in the memory module are incompatible with the firmware type. Example: Memory module of an inverter with an application I/O is used in an inverter with a standard I/O.

Description

EPM data: firmware type incompatible

Keypad display

EPM: FW incomp.

Fault message ID
30353
Severity/response

Fault

  • The data have been loaded into the RAM memory, but they are incompatible.