Skip to main content

0x7694

Remedy

1. Check parameter settings. 2. Reset error. 3. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command.

Cause

The parameter settings saved in the memory module comply with a different hardware. Example: Memory module of an inverter with a power of 3 kW is used in an inverter with a power of 18.5 kW.

Description

EPM data: new PU size detected

Keypad display

EPM new PU size

Fault message ID
30356
Severity/response

Fault

  • The data have been loaded into the RAM memory without being modified, and they are compatible.
  • The settings loaded must be accepted by the user (see remedy).