Skip to main content

0x8115

Remedy
  • Check communication.
  • Check settings of the parameter access monitoring (PAM) function.
Cause

The parameter access monitoring (PAM) function has been activated. For a time longer than the time-out period set in 0x2552:003 (P595.03), no value was entered into the "Keep- alive-Register" 0x2552:002 (P595.02).

Description

Time-out (PAM)

Keypad display

(PAM) Time-out

Fault message ID
33045
Severity/response

No response (configurable) Setting parameters: 0x2552:004 (P595.04)

Severity/response - 2

Setting parameters: 0x2552:004 (P595.04)