0x8182

Remedy
  • Check wiring of the network.
  • Check bus terminating resistor.
  • Set the identical baud rate for each node of the network.
  • Assign a unique node address to each node of the network.
  • Eliminate EMC interferences.
Cause

Too many faulty frames have been received.

  • Defective cable (e. g. loose contact).
  • Two nodes with the same node address.
Description

CAN: bus off

Keypad display

CAN: bus off

Fault message ID
33154
Severity/response

Trouble (configurable)

  • Change to the "Bus-Off" communication status.
Severity/response - 2

Setting parameters: 0x2857:010