Skip to main content

0x3210

Remedy

Reduce dynamic performance of the load profile.

Check mains voltage.

Check settings for brake energy
management.

0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper

Cause

DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01).

Description

Fault - DC bus overvoltage

Keypad display
DC Bus OV
Fault message ID
12816
Severity/response

Fault

Frequency inverter type