8400 protec
The 8400 protec frequency inverter is suitable for decentralized wall mounting and features simple plug-in technology. The decentralized arrangement significantly shortens the length of the motor cables. This enables even complex machines to be structured clearly.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: Turntables and scissor lift tables (intralogistics), monorail overhead conveyors (automotive industry), ...
Highlights
- Easy commissioning with plug technology (plug and drive)
- LED display and status LEDs
- High protection class IP65
Documentation
| Title | Language | Document type | Version | File |
|---|---|---|---|---|
| PLC Designer V3 Application Samples | DE | Commissioning | 2.1 | |
| PLC Designer V3 Application Samples | EN | Commissioning | 2.1 | |
| CANopen 8400 | DE | Operating instructions | 4.2 | |
| CANopen 8400 | EN | Operating instructions | 4.2 |
Error codes
| Cause | Remedy | Severity/response |
|---|---|---|
DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01). |
Reduce dynamic performance of the load profile. Check mains voltage. Check settings for brake energy 0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided. |
Switch back to operation with regular mains voltage |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Mains phase failure |
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
DC bus voltage is lower than specified in C0173. |
|
cawc |
| Cause | Remedy | Severity/response |
|---|---|---|
Braking energy is too high. (DC−bus voltage is higher than set in C0173.) |
|
| Cause | Remedy | Severity/response |
|---|---|---|
|
Check drive dimensioning. |
| Cause | Remedy | Severity/response |
|---|---|---|
|
Check drive dimensioning. |
| Cause | Remedy | Severity/response |
|---|---|---|
|
Check drive dimensioning. |
| Cause | Remedy | Severity/response |
|---|---|---|
One of the motor phases has |
|
| Cause | Remedy | Severity/response |
|---|---|---|
Short circuit Excessive capacitive charging |
|
| Cause | Remedy | Severity/response |
|---|---|---|
Device utilisation (ixt) too high by frequent and too long acceleration processes. |
Check drive sizing.
|
Fault (configurable)
Blocking time: 2 s Setting parameters: 0x2D40:005 (P135.05) |
| Cause | Remedy | Severity/response |
|---|---|---|
Motor thermally overloaded, e. g. by an impermissible continuous current or by frequent or too long acceleration processes. |
Check drive sizing.
|
Fault (configurable)
Blocking time: 2 s Setting parameters: 0x2D4B:003 (P308.03) |
| Cause | Remedy | Severity/response |
|---|---|---|
Short circuit of motor cable |
Check motor cable for short circuit. |
Fault
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
|
|
Fault
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
|
|
Fault
Blocking time: 2 s |