8400 HighLine
The 8400 HighLine frequency inverter is suitable for speed control with simple motion control and positioning tasks.
The requirements of the Ecodesign Directive, Standard EN IEC 61800-9-2, are met.
Application areas: rotary indexing tables, storage systems (intralogistics), form-fill-seal machines (packaging industry), ...
Highlights
- Integrated positioning control
- Up to 15 selectable positioning points including the respective travel profile
- Optionally available with "Safe Torque Off (STO)" with SIL 3 (EN IEC 62061/EN IEC 61508) and Performance Level e (EN ISO 13849-1)
Image
Documentation
| Title | Language | Document type | Version | File |
|---|---|---|---|---|
| "Actuator Torque" technology application | DE | Commissioning | 1.1 | |
| "Actuator Torque" technology application | EN | Commissioning | 1.1 | |
| PLC Designer V3 Application Samples | DE | Commissioning | 2.1 | |
| PLC Designer V3 Application Samples | EN | Commissioning | 2.1 | |
| CANopen 8400 | DE | Operating instructions | 4.2 | |
| CANopen 8400 | EN | Operating instructions | 4.2 | |
| EtherCAT® 8400 E84AYCET | DE | Operating instructions | 3.1 | Document
|
| EtherCAT® 8400 E84AYCET | EN | Operating instructions | 3.1 | Document
|
| EtherNet/IP™ 8400 E84AYCEO | DE | Operating instructions | 3.0 | Document
|
| EtherNet/IP™ 8400 E84AYCEO | EN | Operating instructions | 3.0 | Document
|
| POWERLINK 8400 E84AYCEC | DE | Operating instructions | 3.0 | Document
|
| POWERLINK 8400 E84AYCEC | EN | Operating instructions | 3.0 | Document
|
| PROFIBUS 8400 E84AYCPM | DE | Operating instructions | 2.2 | Document
|
| PROFIBUS 8400 E84AYCPM | EN | Operating instructions | 2.2 | Document
|
| PROFINET 8400 E84AYCER | DE | Operating instructions | 11.0 | Document
|
| PROFINET 8400 E84AYCER | EN | Operating instructions | 11.0 | Document
|
Error codes
| Cause | Remedy | Severity/response |
|---|---|---|
If the "Keypad Full Control" control mode is active. |
To exit the control mode, press the keypad key CTRL. |
Warning
|
| Cause | Remedy | Severity/response |
|---|---|---|
Error when reading the data from the power unit. |
|
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
Error when reading the data from the control unit. |
|
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
Inverter is not compatible with the Controller/PLC (brand protection).
|
Use corresponding (compatible) OEM components. |
Warning
|
| Cause | Remedy | Severity/response |
|---|---|---|
A wrong password has been entered several times. |
Wait until the blocking time has elapsed and then enter the correct password. |
Warning
|
| Cause | Remedy | Severity/response |
|---|---|---|
If "manual operation" is active, an error is generated in case the communication links get lost. |
The error can be only be reset if the connection is restored or the control mode is changed to a different value than "manual operation". |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
Indicates the activation of the manual speed control. |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Indicates the deactivation of the manual speed control. |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
|
Check application. |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
If the apparent motor current exceeds a defined threshold value 0x4007:002 for a certain amount of time 0x4007:001, heavy duty monitoring is triggered. |
Check the motor load. |
No response (configurable) Setting parameters: 0x4007:003 Setting parameters: 0x4007:003 |
| Cause | Remedy | Severity/response |
|---|---|---|
In a running motor, the motor load (current) is monitored. When the motor load falls below the threshold value specified in Load loss detection: threshold (0x4006:001 (P710.01)) for the period of time specified in Load loss detection: delay time (0x4006:002 (P710.02)), load loss protection is triggered. |
Check utilisation |
No response (configurable) Setting parameters: 0x4006:003 (P710.03) Setting parameters: 0x4006:003 (P710.03) |
| Cause | Remedy | Severity/response |
|---|---|---|
At mains connection, a start command was already available and the automatic start at power-up is set in 0x2838:002 (P203.02) to "Off [0]". |
Deactivate starting command and reset error. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The calculated thermal load of the brake resistor has reached the warning threshold set in 0x2550:008 (P707.08). The regenerative energy is too high. |
|
Warning (configurable) Setting parameters: 0x2550:010 (P707.10) Setting parameters: 0x2550:010 (P707.10) |
| Cause | Remedy | Severity/response |
|---|---|---|
Cascade function for pumps and fans The maximum frequency in 0x2916 (P211.00) has been reached and no free additional pump is available. |
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Configuration or runtime error |
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
During the automatic identification of the motor, an error has occurred. |
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
A failure of the motor phase W has been detected. |
|
No response (configurable)
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
A failure of the motor phase V has been detected. |
|
No response (configurable)
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
A failure of the motor phase U has been detected. |
|
No response (configurable)
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
A failure of several motor phases has been detected. |
|
No response (configurable)
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
The motor speed has reached the error threshold for overspeed set in 0x2D44:001 (P350.01). |
Adapt the maximum motor speed 0x6080 (P322.00) and the warning threshold or error threshold 0x2D44:001 (P350.01). |
Fault (configurable)
Blocking time: 1 s |
| Cause | Remedy | Severity/response |
|---|---|---|
The safety module or safety circuit of the device was detected as being defective. The integrated safety technology is defective. |
Hardware error: it is necessary to contact the manufacturer since the device must be replaced. The inverter must be replaced. Note! The user is not allowed to change inverters that come with integrated safety technology.
|
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The calculated thermal load of the brake resistor has reached the error threshold set in 0x2550:009 (P707.09). The regenerative energy is too high. |
|
Fault (configurable)
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
The keypad was removed while the keypad control was activated. |
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The selected function is not permissible in the chosen operating mode.
|
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Motor has reached the torque limit:
|
|
No response (configurable) Setting parameters: 0x2D67:001 (P329.01) |
| Cause | Remedy | Severity/response |
|---|---|---|
RPDO3 was not received within the time-out period set in 0x1402:005 (P542.05) or with the sync configured. |
Fault (configurable) Setting parameters: 0x2857:003 |
| Cause | Remedy | Severity/response |
|---|---|---|
RPDO2 was not received within the time-out period set in 0x1401:005 (P541.05) or with the sync configured. |
Fault (configurable) Setting parameters: 0x2857:002 |
| Cause | Remedy | Severity/response |
|---|---|---|
RPDO1 was not received within the time-out period set in 0x1400:005 (P540.05) or with the sync configured. |
Fault (configurable) Setting parameters: 0x2857:001 |
| Cause | Remedy | Severity/response |
|---|---|---|
|
Check data mapping in the master and slave. |
Trouble (configurable) Setting parameters: 0x2859:003 (P515.03) Setting parameters: See details for 33414 |
| Cause | Remedy | Severity/response |
|---|---|---|
CRC frame defective. |
Check system setup. |
Trouble (configurable) Setting parameters: 0x2859:010 |
| Cause | Remedy | Severity/response |
|---|---|---|
SoC of master was not received. |
Check configuration and system setup. |
Trouble (configurable) Setting parameters: 0x2859:011 |
| Cause | Remedy | Severity/response |
|---|---|---|
In case of the Ethernet communication interface, an internal software error has occurred. |
|
Trouble |
| Cause | Remedy | Severity/response |
|---|---|---|
The request by the master is invalid, e. g. invalid CRC checksum, non-supported function code, or impermissible data access. |
Check request by the master:
|
Warning The inverter (slave) responds to the master with an error code:
|
| Cause | Remedy | Severity/response |
|---|---|---|
No valid messages have been received via the Modbus for a longer time than the time-out time set in 0x2858:002 (P515.02). |
|
Fault (configurable) Setting parameters: 0x2858:001 (P515.01) |
| Cause | Remedy | Severity/response |
|---|---|---|
The cyclic process data received are invalid. |
Check cyclic process data sent by the master. |
Trouble (configurable) Setting parameters: See details for 33171 |
| Cause | Remedy | Severity/response |
|---|---|---|
The initialisation of the communication stack has been interrupted due to an incorrect address setting or communication configuration. |
Check master/slave configuration and restart the devices. |
Trouble (configurable) Setting parameters: See details for 33170 |
| Cause | Remedy | Severity/response |
|---|---|---|
The communication partner has interrupted the cyclic data exchange. |
|
No response (configurable) Setting parameters: 0x2859:002 (P515.02) |
| Cause | Remedy | Severity/response |
|---|---|---|
Time-out during cyclic data reception, e.g. due to an interrupted communication link to the master or missing cyclic data. |
|
Trouble (configurable) Setting parameters: See details for 33168 |
| Cause | Remedy | Severity/response |
|---|---|---|
Within the heartbeat time 0x1016:004 (P520.04), no heartbeat telegram was received by node 4 to be monitored. |
|
Fault (configurable) Setting parameters: 0x2857:008 |
| Cause | Remedy | Severity/response |
|---|---|---|
Within the heartbeat time 0x1016:003 (P520.03), no heartbeat telegram was received by node 3 to be monitored. |
|
Fault (configurable) Setting parameters: 0x2857:007 |
| Cause | Remedy | Severity/response |
|---|---|---|
Within the heartbeat time 0x1016:002 (P520.02), no heartbeat telegram was received by node 2 to be monitored. |
|
Fault (configurable) Setting parameters: 0x2857:006 |
| Cause | Remedy | Severity/response |
|---|---|---|
Within the heartbeat time 0x1016:001 (P520.01), no heartbeat telegram was received by node 1 to be monitored. |
|
Fault (configurable) Setting parameters: 0x2857:005 |
| Cause | Remedy | Severity/response |
|---|---|---|
Too many faulty frames have been received.
|
|
Warning (configurable) Setting parameters: 0x2857:011 |
| Cause | Remedy | Severity/response |
|---|---|---|
Too many faulty frames have been received.
|
|
Trouble (configurable)
Setting parameters: 0x2857:010 |
| Cause | Remedy | Severity/response |
|---|---|---|
For a time longer than the time-out period set in 0x23B6:002 (P514.02), no value was entered into the Keep alive register 0x23B6:005 (P514.05). |
Check communication with the master. |
Fault (configurable) Setting parameters: 0x2859:009 (P515.09) Setting parameters: 0x2859:009 (P515.09) |
| Cause | Remedy | Severity/response |
|---|---|---|
No valid messages have been received by the Modbus master for a time longer than the time- out period set in 0x23B6:001 (P514.01). |
Check communication with the master. |
Fault (configurable) Setting parameters: 0x2859:008 (P515.08) Setting parameters: 0x2859:008 (P515.08) |
| Cause | Remedy | Severity/response |
|---|---|---|
The parameter access monitoring (PAM) function has been activated. For a time longer than the time-out period set in 0x2552:003 (P595.03), no value was entered into the "Keep- alive-Register" 0x2552:002 (P595.02). |
|
No response (configurable) Setting parameters: 0x2552:004 (P595.04) Setting parameters: 0x2552:004 (P595.04) |
| Cause | Remedy | Severity/response |
|---|---|---|
|
|
Warning (configurable) Setting parameters: 0x2859:007 (P515.07) |
| Cause | Remedy | Severity/response |
|---|---|---|
|
|
Warning (configurable) Setting parameters: 0x2859:006 (P515.06) Setting parameters: 0x2859:006 (P515.06) |
| Cause | Remedy | Severity/response |
|---|---|---|
A voltage failure has occurred and changed parameter settings that had not been saved yet were available. |
1. Execute parameter settings again. 2. Execute device command "Save user data" 0x2022:003 (P700.03). |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The memory module contains parameter settings for one or several parameters that are not known to the inverter. |
Execute the "Save user data" 0x2022:003 (P700.03) device command. This reinitialises the user memory with the current parameter settings. In this way, parameter settings that are no longer required are automatically deleted. |
Information |
| Cause | Remedy | Severity/response |
|---|---|---|
One or more parameters can no longer be used for the "Parameter change-over" function. |
1. Check error message for parameter change- over in 0x4047:001 (P756.01). 2. Correct the list entry shown in 0x4047:002 (P756.02). |
Warning
|
| Cause | Remedy | Severity/response |
|---|---|---|
The parameter settings saved in the memory module comply with a different hardware. Example: Memory module of an inverter with a power of 3 kW is used in an inverter with a power of 18.5 kW. |
1. Check parameter settings. 2. Reset error. 3. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command. |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The parameter settings saved in the memory module are incompatible with the inverter. |
1. Execute device command "Load default settings" 0x2022:001 (P700.01). 2. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command. |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The parameter settings saved in the memory module do not match the inverter hardware. |
1. Check parameter settings. 2. Reset error. 3. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command. |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The parameter settings saved in the memory module are incompatible with the firmware type. Example: Memory module of an inverter with an application I/O is used in an inverter with a standard I/O. |
1. Execute device command "Load default settings" 0x2022:001 (P700.01). 2. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command. |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The parameter settings saved in the memory module are incompatible with the firmware version. |
1. Execute device command "Load default settings" 0x2022:001 (P700.01). 2. Execute "Save user data" 0x2022:003 (P700.03) or "Save OEM data" 0x2022:006 (P700.06) device command. |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The memory module connected is not supported by the inverter. |
1. Switch off inverter. 2. Replace plugged-in memory module by a memory module that matches the inverter. 3. Switch the inverter on again. |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The OEM memory contains invalid parameter settings or is empty. |
|
Warning
|
| Cause | Remedy | Severity/response |
|---|---|---|
Saving of the parameter settings was interrupted by an unexpected disconnection. |
1. Check user parameter settings. (The loaded backup is an older version.) 2. If required, repeat the changes made last. 3. Execute device command "Save user data" 0x2022:003 (P700.03). |
Warning
|
| Cause | Remedy | Severity/response |
|---|---|---|
The user parameter settings in the memory module are invalid. |
1. Execute user parameter settings again. 2. Execute device command "Save user data" 0x2022:003 (P700.03). |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The inverter memory module was removed. |
1. Switch off inverter. 2. Plug the memory module into the inverter. 3. Switch the inverter on again. Note: The memory module cannot be replaced during ongoing operation! |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The memory module contains too many parameter settings. |
Execute "Save user data" 0x2022:003 (P700.03) device command again. This reinitialises the user memory with the current parameter settings. In this way, parameter settings that are no longer required are automatically deleted. |
Warning
|
| Cause | Remedy | Severity/response |
|---|---|---|
The feedback system exceeds the maximum permissible frequency range of the digital inputs. |
Check feedback system. |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
The encoder signal loss monitoring function has detected a failure of the encoder signal. |
|
Warning (configurable) Setting parameters: 0x2C45 (P342.00) Setting parameters: 0x2C45 (P342.00) |
| Cause | Remedy | Severity/response |
|---|---|---|
The motor current has exceeded the warning/ error threshold for the motor current monitoring set in 0x2D46:001 (P353.01). |
|
Fault (configurable)
Blocking time: 1 s Setting parameters: 0x2D46:002 (P353.02) |
| Cause | Remedy | Severity/response |
|---|---|---|
|
|
Fault (configurable) Setting parameters: 0x2C60 Setting parameters: 0x2C60 |
| Cause | Remedy | Severity/response |
|---|---|---|
Open circuit or short circuit at analog output 2. |
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Open circuit or short circuit at analog output 1. |
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
No response (configurable) Setting parameters: 0x2641:006 (P416.06) Setting parameters: 0x2641:006 (P416.06) |
| Cause | Remedy | Severity/response |
|---|---|---|
The monitoring function of the input signal configured for analog input 2 in 0x2637:008 (P431.08) and 0x2637:009 (P431.09) has been triggered. |
|
Fault (configurable) Setting parameters: 0x2637:010 (P431.10) Setting parameters: 0x2637:010 (P431.10) |
| Cause | Remedy | Severity/response |
|---|---|---|
The monitoring function of the input signal configured for analog input 1 in 0x2636:008 (P430.08) and 0x2636:009 (P430.09) has been triggered. |
|
Fault (configurable) Setting parameters: 0x2636:010 (P430.10) Setting parameters: 0x2636:010 (P430.10) |
| Cause | Remedy | Severity/response |
|---|---|---|
The last setting of the connection level differs from the saved setting. |
1. Execute device command "Save user data" 0x2022:003 (P700.03). 2. Switch inverter off and on again. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The power unit installed is not supported by the software. |
Update firmware of the inverter to the most recent version. |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
Calibration data of the power unit not compatible or faulty. |
|
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
Calibration data of the control unit not compatible or faulty. |
|
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
The “Back-to-Box” system command has been executed. The standard parameter set has been written and saved. Communication is deactivated and the device is in stop status. |
Switch inverter off and on again. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The device ID of the device was changed manually. |
1. Execute device command "Save user data" 0x2022:003 (P700.03). 2. Switch inverter off and on again. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
Two bits of the NetWordIN1 data word 0x4008:001 (P590.01) were assigned to the same function. |
Check and correct configuration of the NetWordIN1 data word.
|
Trouble |
| Cause | Remedy | Severity/response |
|---|---|---|
The "Activate fault 2" function was triggered via the NetWordIN1 data word 0x4008:001 (P590.01). |
Eliminate error cause and then reset error. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The "Activate fault 1" function was triggered via the NetWordIN1 data word 0x4008:001 (P590.01). |
Eliminate error cause and then reset error. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The "Activate fault" function was triggered via bit 10 of the LECOM control word 0x400B:002 (P592.02). |
Eliminate error cause and then reset error. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The number of permitted restart attempts after a fault set in 0x2839:003 (P760.03) was exceeded. The fault occurred to frequently and could not be reset. |
Check and the eliminate the fault. |
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
|
|
Warning
|
| Cause | Remedy | Severity/response |
|---|---|---|
Flexible I/O configuration: the "Activate fault 2" function was activated via the trigger selected in 0x2631:044 (P400.44). |
Eliminate error cause and then reset error. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
Flexible I/O configuration: the "Activate fault 1" function was activated via the trigger selected in 0x2631:043 (P400.43). |
Eliminate error cause and then reset error. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The assignment directives have not been observed.
|
Check and correct the assignment of the triggers to the functions.
|
Trouble |
| Cause | Remedy | Severity/response |
|---|---|---|
Warning of the internal fan. |
Check/replace internal fan. |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
The control unit (OEM hardware) is not compatible with the power unit (OEM hardware). |
|
Fault
|
| Cause | Remedy | Severity/response |
|---|---|---|
Output current at the 24V output or at the digital outputs too high. |
Check 24V output and digital outputs for earth fault or overload. |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
External supply voltage failed or too low. |
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
The motor temperature sensor connected to terminals X109/T1 and X109/T2 measures a too high motor temperature.
|
|
Fault (configurable)
Blocking time: 2 s Setting parameters: 0x2D49:002 (P309.02) |
| Cause | Remedy | Severity/response |
|---|---|---|
The heatsink temperature of the power unit (display in 0x2D84:001 (P117.01)) has exceeded the warning threshold set in 0x2D84:002.
|
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Warning of the heatsink fan. |
Clean fan and ventilation slots. If required, replace fan. The fans can be unlocked via locking hooks and can then be removed. |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Sensor for the temperature monitoring of the power unit is defective. The failure of the temperature monitoring function poses the risk of overheating! |
Hardware error: it is necessary to contact the manufacturer, since the device must be replaced. |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The heatsink temperature of the power unit (display in 0x2D84:001 (P117.01)) has exceeded the fixed error threshold (100 °C).
|
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
The input voltage is too low to switch on the inverter. |
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
DC-bus voltage has fallen below the warning threshold for undervoltage set in 0x2540:002 (P208.02). |
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
DC-bus voltage has fallen below the error threshold for undervoltage. The error threshold (display in 0x2540:003 (P208.03)) results from the setting of the rated mains voltage in 0x2540:001 (P208.01). |
|
Trouble |
| Cause | Remedy | Severity/response |
|---|---|---|
DC-bus voltage has exceeded the warning threshold for overvoltage set in 0x2540:005 (P208.05) due to a too high braking energy or a too high mains voltage. |
|
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
The actual current0x6078 (P103.00) is equal to or higher than the max. current 0x6073 (P324.00). |
|
Information |
| Cause | Remedy | Severity/response |
|---|---|---|
Maximum current of the axis (display in 0x2DDF:002) has been reached too often in succession. |
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
Overload of the motor with sensorless control for synchronous motors (SL-PSM). |
|
Trouble
|
| Cause | Remedy | Severity/response |
|---|---|---|
Device utilisation (ixt) too high by frequent and too long acceleration processes. |
Check drive dimensioning. |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
DC-bus voltage has exceeded the error threshold for overvoltage due to a too high braking energy or a too high mains voltage. The error threshold (display in 0x2540:006 (P208.06) results from the setting of the rated mains voltage in 0x2540:001 (P208.01). |
Reduce dynamic performance of the load profile. Check mains voltage. Check settings for brake energy 0x2541:001 (P706.01) = [0]: Connect brake resistor to the power unit and activate the integrated brake chopper |
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
Operation on uninterrupted 1x230V current supply (UPS) has been activated: Only a reduced output current is provided. |
Switch back to operation with regular mains voltage |
Warning |
| Cause | Remedy | Severity/response |
|---|---|---|
Mains phase failure |
|
Fault |
| Cause | Remedy | Severity/response |
|---|---|---|
DC bus voltage is lower than specified in C0173. |
|
cawc |
| Cause | Remedy | Severity/response |
|---|---|---|
Braking energy is too high. (DC−bus voltage is higher than set in C0173.) |
|
| Cause | Remedy | Severity/response |
|---|---|---|
|
Check drive dimensioning. |
| Cause | Remedy | Severity/response |
|---|---|---|
|
Check drive dimensioning. |
| Cause | Remedy | Severity/response |
|---|---|---|
|
Check drive dimensioning. |
| Cause | Remedy | Severity/response |
|---|---|---|
One of the motor phases has |
|
| Cause | Remedy | Severity/response |
|---|---|---|
Short circuit Excessive capacitive charging |
|
| Cause | Remedy | Severity/response |
|---|---|---|
Device utilisation (ixt) too high by frequent and too long acceleration processes. |
Check drive sizing.
|
Fault (configurable)
Blocking time: 2 s Setting parameters: 0x2D40:005 (P135.05) |
| Cause | Remedy | Severity/response |
|---|---|---|
Motor thermally overloaded, e. g. by an impermissible continuous current or by frequent or too long acceleration processes. |
Check drive sizing.
|
Fault (configurable)
Blocking time: 2 s Setting parameters: 0x2D4B:003 (P308.03) |
| Cause | Remedy | Severity/response |
|---|---|---|
Short circuit of motor cable |
Check motor cable for short circuit. |
Fault
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
|
|
Fault
Blocking time: 2 s |
| Cause | Remedy | Severity/response |
|---|---|---|
|
|
Fault
Blocking time: 2 s |