Quick start – i510/i550 frequency inverter

Operation of keypad
I/O settingGROUP 4Fct. dig. outputsP420.XXDO1 functionP420.02Release brake115Running50
Group 0 – Favourites
Group 1 – Diagnostics
Group 2 – Basic setting
Group 3 – Motor control
Group 4 – I/O setting
Group 5 – Network setting
Group 6 – Process controller
Group 7 – Additional functions
Group 8 – Sequencer

Navigation in the menu
Parameter alteration
Go to Menu/Parameters
Confirm parameter
Quit Menu/Parameters
CTRLKeypad control
Start motor
RFChange direction of rotation
Stop motor
Group 0 - Favourites: Quick access to most important parameters (*)
Procedure during commissioning
1. Load default setting: Set P700.01 = 1
2. Select language: P705.00 (1 = English; 2 = German)
3. Basic setting V/f characteristic control:
*P208.01 Set mains voltage
*P303.01 Basic voltage = Rated motor voltage
*P303.02 Basic frequency = Rated motor frequency
*P210.00 Minimum frequency [Hz]
*P211.00 Maximum frequency [Hz]
*P220.00 Acceleration time [s]
*P221.00 Deceleration time [s]
*P430.02 Analog input 1: Min frequency value [Hz]
*P430.03 Analog input 1: Max frequency value [Hz]
FrequencyTimeAI1P211.00P430.03P220.00P221.00P430.02P210.00P430.02
Control of inverter by means of keypad
Set parameters:
*P200.00 = 1 (Keypad as control source)   or  CTRL
*P201.01 = 1 (Keypad as setpoint source)
Operation:
RFReverse direction of rotation

Change frequency setpoint
Start/stop motor
Connection I/O terminals:
GND
AI1
AI2
AO1
10V
24V24 VDC, 100 mA supply
DI1Start enabling
Control of inverter by means of terminals (default setting)
Set parameters:
*P450.01 Frequency setpoint presets: Freq. preset 1 [Hz]
*P450.02 Frequency setpoint presets: Freq. preset 2 [Hz]
*P450.03 Frequency setpoint presets: Freq. preset 3 [Hz]
Connection I/O terminals:
GNDGND
AI1Frequency setpoint
AI2Input range [Hz]: *P430.02 - *P430.03
AO1
10V10 VDC supply
24V24 VDC, 100 mA supply
DI1Start
DI2Reset error (optional)
DI3Reverse direction of rotation (Optional)
DI4Activate preset (Bit 0) (Optional)
DI5Activate preset (Bit 1) (Optional)
Save parameter settings in the user memory of the memory module
Save parameter settings:
Press keypad enter key longer than 3 s
Keypad display:
SET↵  flashes = Parameter settings not saved
on = Parameter settings saved
Flexible I/O configuration
24EOptional external 24 V supply (only i550)
GNDGND for analog and digital signals
Default setting
*P201.01
(configured AI1 as
standard setpoint)
AI1Analog input 1  
Config.:  *P430.01 (0 ... 10 VDC signal)
AI2Analog input 2  
Range [Hz]:  *P430.02 - *P430.03
AO1Analog output 1
10V10 VDC, supply for potentiometer
24V24 VDC, 100 mA supply, reference for digital inputs
*P400.02 StartDI1Digital input 1
*P400.04 Reset errorDI2Digital input 2
*P400.13 Reverse direction of rotationDI3Digital input 3
*P400.18 Activate preset (bit 0)DI4Digital input 4
*P400.19 Activate preset (bit 1)DI5Digital input 5
*P420.02 DO1 triggered when
Release brake
DO1Digital output 1
GNDGND for analog and digital signals
*P420.01 Relay triggered when
Ready for operation set
NORelay NO-contact
COMRelay Middle contact
NCRelay NC-contact
bit 1bit 0Frequency presets
01Preset 01 (*P450.01)
10Preset 02 (*P450.02)
11Preset 03 (*P450.03)
• Set Standard setpoint source (*P201.01).
Activate quick stop (*P400.03): Brings the motor to a standstill within the deceleration time set in P225.00.
Jog forwards (P400.10) and Jog reverse (P400.11): Initiate status-controlled motor rotation forwards with frequency preset 05 (P450.05) or reverse with frequency preset 06 (P450.06).
Reverse direction of rotation (*P400.13): Invert frequency setpoint.
Diagnostics
*P100.00 Output frequency [Hz]
P102.00 Frequency setpoint [Hz]
*P103.00 Actual current [%]
(100 % = Rated motor current)
P125.01 Active control source
P125.02 Active setpoint source
LED “RDY” (blue)LED “ERR” (red)State/meaning
offoffNo supply voltage
Initialisation (inverter is started)
blinking
offSafe torque off (STO) active. The inverter has been disabled by the integrated functional safety. (Optional, i550 only)
blinking fast
Safe torque off (STO) active, warning present. The inverter has been disabled by the integrated functional safety. (Optional, i550 only)
blinking
offInverter disabled
blinking fast
Inverter disabled, warning present.
Inverter disabled, error active.
on briefly every 1.5 s
Inverter disabled, no DC-bus voltage.
offInverter enabled. The motor rotates according to the specified setpoint or quick stop active.
blinking fast
Inverter enabled, warning present. The motor rotates according to the specified setpoint or quick stop active.
blinking
Inverter enabled, quick stop active as response to a fault.
Error messageCause (W. = Warning, T. = Fault, F. = Error)Remedy
.2382/.2383Ixt error/Ixt warningReduce load, adapt ramps
.3210/.3211Overvoltage DC bus/
Warning Overvoltage DC bus
Reduce dynamic performance of the load profile, check mains voltage, check settings for brake energy management
.3220/.3221Undervoltage DC bus/
Warning Undervoltage DC bus
Check mains voltage, check DC-bus voltage (P105.00), check mains settings, check fuses
.3222DC-bus voltage to low for switch-on
.4310Motor overtemperature problem (PTC)Check ambient temperature and motor load
.6280Trigger/functions incorrectly connectedIn the case of Flexible I/O configuration (*P200.01), Inverter enable (*P400.01) or Start (*P400.02) must have been assigned to an I/O. Do not use Start forwards/reverse and Run forwards/reverse at the same time!
.FF37Automatic start inhibitedDeactivate starting command and reset error