Operation of keypad
Group 0 – Favourites Group 1 – Diagnostics Group 2 – Basic setting Group 3 – Motor control Group 4 – I/O setting Group 5 – Network setting Group 6 – Process controller Group 7 – Additional functions Group 8 – Sequencer |
|
|||||||||||||||
Group 0 - Favourites: Quick access to most important parameters (*) |
||||||||||||||||
| Procedure during commissioning | |
| 1. Load default setting: Set P700.01 = 1 2. Select language: P705.00 (1 = English; 2 = German) 3. Basic setting V/f characteristic control: *P208.01 Set mains voltage *P303.01 Basic voltage = Rated motor voltage *P303.02 Basic frequency = Rated motor frequency *P210.00 Minimum frequency [Hz] *P211.00 Maximum frequency [Hz] *P220.00 Acceleration time [s] *P221.00 Deceleration time [s] *P430.02 Analog input 1: Min frequency value [Hz] *P430.03 Analog input 1: Max frequency value [Hz] | |
|
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| Save parameter settings in the user memory of the memory module | ||
| Save parameter settings: Press keypad enter key longer than 3 s |
Keypad display: SET↵ flashes = Parameter settings not saved on = Parameter settings saved | |
| Flexible I/O configuration | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
• Set Standard setpoint source (*P201.01).
• Activate quick stop (*P400.03): Brings the motor to a standstill within the deceleration time set in P225.00.
• Jog forwards (P400.10) and Jog reverse (P400.11): Initiate status-controlled motor rotation forwards with frequency preset 05 (P450.05) or reverse with frequency preset 06 (P450.06).
• Reverse direction of rotation (*P400.13): Invert frequency setpoint.
• Activate quick stop (*P400.03): Brings the motor to a standstill within the deceleration time set in P225.00.
• Jog forwards (P400.10) and Jog reverse (P400.11): Initiate status-controlled motor rotation forwards with frequency preset 05 (P450.05) or reverse with frequency preset 06 (P450.06).
• Reverse direction of rotation (*P400.13): Invert frequency setpoint.
| Diagnostics | ||
| *P100.00 Output frequency [Hz] P102.00 Frequency setpoint [Hz] |
*P103.00 Actual current [%] (100 % = Rated motor current) |
P125.01 Active control source P125.02 Active setpoint source |
| LED “RDY” (blue) | LED “ERR” (red) | State/meaning |
| off | off | No supply voltage |
| Initialisation (inverter is started) | ||
blinking | off | Safe torque off (STO) active. The inverter has been disabled by the integrated functional safety. (Optional, i550 only) |
blinking fast | Safe torque off (STO) active, warning present. The inverter has been disabled by the integrated functional safety. (Optional, i550 only) | |
blinking | off | Inverter disabled |
blinking fast | Inverter disabled, warning present. | |
| Inverter disabled, error active. | ||
on briefly every 1.5 s | Inverter disabled, no DC-bus voltage. | |
| off | Inverter enabled. The motor rotates according to the specified setpoint or quick stop active. | |
blinking fast | Inverter enabled, warning present. The motor rotates according to the specified setpoint or quick stop active. | |
blinking | Inverter enabled, quick stop active as response to a fault. |
| Error message | Cause (W. = Warning, T. = Fault, F. = Error) | Remedy |
| .2382/.2383 | Ixt error/Ixt warning | Reduce load, adapt ramps |
| .3210/.3211 | Overvoltage DC bus/ Warning Overvoltage DC bus | Reduce dynamic performance of the load profile, check mains voltage, check settings for brake energy management |
| .3220/.3221 | Undervoltage DC bus/ Warning Undervoltage DC bus | Check mains voltage, check DC-bus voltage (P105.00), check mains settings, check fuses |
| .3222 | DC-bus voltage to low for switch-on | |
| .4310 | Motor overtemperature problem (PTC) | Check ambient temperature and motor load |
| .6280 | Trigger/functions incorrectly connected | In the case of Flexible I/O configuration (*P200.01), Inverter enable (*P400.01) or Start (*P400.02) must have been assigned to an I/O. Do not use Start forwards/reverse and Run forwards/reverse at the same time! |
| .FF37 | Automatic start inhibited | Deactivate starting command and reset error |